3142

UL3142 is UL recognized wire, 3142 is the style number, as one of the appliance wiring material (AWM) family. UL3142 consists of copper conductor and silicone rubber insulation. It is typically used for internal wiring, with rated 150 Celsius degrees and voltage 600V.

Category: Tag:

Description

UL3142 is a member of the UL wire family, rated 150℃ and 600V.

Parameters

  • Style number: UL3142
  • Rated temperature: 150℃
  • Rated voltage: 600V
  • Conductor material: stranded copper, or solid copper
  • Insulation material: quality silicone rubber
  • Use standard: AWM, UL758, UL3142
  • Application: internal wiring of electrical appliance.

Specification

UL3142 Wire Gauge Conductor Structure Insulation
Thickness
Overall
Diameter
Standard Package Minimum Package Conductor
Resistance
(Cond Type) (AWG) (No/mm) (mm) (mm) (Feet) (Meters) (Ω/KM)
Stranded 18 7/0.39 1.524 4.39 2000 610 23.20
Stranded 18 34/0.178 1.524 4.39 2000 610 23.20
Stranded 16 7/0.50 1.524 4.69 1000 305 14.60
Stranded 16 26/0.25 1.524 4.69 1000 305 14.60
Stranded 14 37/0.26 1.524 5.07 1000 305 8.96
Stranded 14 41/0.25 1.524 5.07 1000 305 8.96
Stranded 12 45/0.32 1.524 5.56 1000 305 5.64
Stranded 12 65/0.25 1.524 5.56 1000 305 5.64
Solid 18 1/1.02 1.524 4.39 2000 610 21.80
Solid 16 1/1.29 1.524 4.69 1000 305 13.70
Solid 14 1/1.63 1.524 5.07 1000 305 8.62
Solid 12 1/2.05 1.524 5.56 1000 305 5.43